Flow rate is how much hot water a tankless heater can deliver at once, measured in gallons per minute. The number on a brochure is usually the best case, with warm incoming water and a modest temperature rise. In winter, with colder water, the same unit delivers less.
To size a unit correctly you need two numbers: the flow you want at the fixtures and the temperature rise your water needs. Then you compare them with the capacity of the unit at that rise, not the headline figure.
Flow rate and temperature rise
Temperature rise is the difference between the temperature of the incoming water and the temperature you set. If the incoming water is 60 degrees Fahrenheit and you set 120, the rise is 60 degrees. The heater can only add so much heat per minute, so a bigger rise means a lower flow.
A gas unit rated at 199,000 Btu per hour that is about 80 percent efficient delivers roughly 160,000 Btu per hour to the water. Each gallon per minute needs about 500 Btu per hour for every degree of rise. That gives roughly 9 gallons per minute at a 35 degree rise and roughly 4.5 gallons per minute at a 70 degree rise.
| Incoming water | Set temperature | Rise | Approximate flow |
|---|---|---|---|
| Water at 85 degrees F | 120 degrees F | 35 degrees | About 9 gallons per minute. |
| Water at 70 degrees F | 120 degrees F | 50 degrees | About 6 gallons per minute. |
| Water at 60 degrees F | 120 degrees F | 60 degrees | About 5.3 gallons per minute. |
| Water at 50 degrees F | 120 degrees F | 70 degrees | About 4.5 gallons per minute. |
Those figures are arithmetic examples for a unit of that size, not a promise for any one model. Always check the capacity table in your unit's manual for your own rise.
Adding up your fixtures
Make a list of what might run at once. The City of Pleasanton's bathroom handout lists a showerhead at 1.8 gallons per minute at 80 psi, a bathroom faucet at 1.2 gallons per minute and a kitchen faucet at 1.8. Dishwashers and washing machines vary, so read their labels.
Two showers and a running kitchen faucet add up to about 5.4 gallons per minute of mixed water, though the hot portion is less because cold water is blended in at the valve. If your peak demand is higher than the unit can deliver at your rise, you need a larger unit, two units or a different plan.
A simple sizing worksheet
- List every hot water fixture that may run at the same time.
- Add their gallons per minute to get peak flow.
- Estimate your coldest incoming water temperature and choose a set point, often 120 degrees.
- Subtract to get the rise, then find the unit's capacity at that rise.
- Pick a unit whose capacity at that rise is higher than your peak flow.
Why a unit seems to give less flow than it should
| Symptom | Likely cause | What helps |
|---|---|---|
| Flow is weak at one fixture | Clogged aerator or showerhead | Clean the screen. |
| Flow drops at all fixtures over a year | Scale in the heat exchanger | Flush and descale. |
| Hot water cools when a second fixture opens | Demand exceeds capacity at your rise | Reduce use or add capacity. |
| Heater cycles on and off | Flow below the firing minimum | Raise flow or clean the filter. |
| Long wait at far bathroom | Pipe run length | Recirculation pump. |
Minimum flow, the other number that matters
Every unit has a minimum flow, often around half a gallon per minute, below which the burner will not fire. If you open a tap just a little, the heater may not start, and the water stays cold. That explains why a trickle at a bathroom sink sometimes gives only cold water.
A recirculation loop or a small buffer tank can help in these cases. Our tankless water heater page covers flushing, error codes and the choice between a loop and a buffer tank.
When tankless is not the right choice
A tankless unit is a strong choice for steady, long loads and for a house that wants more space. It is a weaker choice for a very large household with many fixtures, or a house with a gas line that cannot be upsized. In those cases, a larger tank or a heat pump heater may be the better fit.
See water heater installation for the planning checklist and replacement if your current heater has already failed.
A worked example for a four-person household
Take a family with two bathrooms that often run two showers at once while someone loads the dishwasher. Two showers at 1.8 gallons per minute add up to 3.6, and the dishwasher adds a modest amount. If the coldest incoming water is about 60 degrees and the set point is 120, the unit must deliver that flow at a 60 degree rise.
A unit that delivers about 5.3 gallons per minute at that rise covers it with a little margin. A smaller unit might manage one shower at a time and struggle with two. That is the kind of mismatch that a sizing worksheet catches before you buy.
Where we work near Pleasanton
We size and service tankless units in Pleasanton and nearby towns, including San Ramon and Dublin. Call the 24/7 line for a failed unit, or book a visit to review sizing.
Questions we hear from callers
Yes. The City of Pleasanton's report lists hardness from 100 to 450 mg/L depending on the source. Scale builds inside the heat exchanger and narrows the passages, so flushing once a year protects flow.
Add the flow of the fixtures that may run at once. A shower at 1.8, a kitchen faucet at 1.8 and a bathroom faucet at 1.2 total 4.8 gallons per minute before blending.
Colder incoming water means a bigger temperature rise, and the heater can only add so much heat per minute.
Often yes for a larger unit, but check capacity at your rise. We size it for your fixtures.
It varies by model, and the manual lists it. Below that flow, the burner will not fire.